Application: Dual certified flameproof Ex d and Increased Safety Ex e indoor and outdoor cable gland for armoured and braided (SY) and steel tape armoured cable providing a flameproof seal on the outer sheath for use in Zone 1, Zone 2, Zone 21, and Zone 22 hazardous areas.
ATEX Certificate No: ITS12ATEX17637
Protection class: II 2 GD Ex d llC Gb / Ex e llC Gb -20°C <Ta <100°C Ex tb lllC -20°C <Ta 100°C Db lP67
Ingress protection: IP67
Operating temp: -20°c to +100°c
Construction & Test standard: EN 60079-0:2009, EN 60079-1: 2007 and EN 60079-3'1:200
Gland body material: Brass - BS 2874 CZ114 / IS 319 gr.1 also available Nickel Plated
Gland must be used as part of a certified assembly in surface installations only. Gland may not be used on a group IIC Ex d Enclosure that is larger than 2000cc volume.
Pack content: Gland(s), brass locknut(s), earth tag(s), and shroud(s)